Results are reported from experiments in which steep-front, short- duration (SFSD) voltage impulses were imposed on various electrical distribution components. These pulses were generated by switching a section of charged, high voltage coaxial cable across the component under study. Components included underground distribution cable, terminators, insulators and arresters. SFSD voltage needed to flashover 15 kV polyethylene cable with a single pulse is approximately 625 kV peak. Strength of polyethylene cable decreases with increasing number of SFSD pulses, indicating cumulative degradation of the polymer. For 15 kV and 25 kV cable terminators, the SFSD CFO was over twice the rated standard lightning BIL for the same units. Similarly, porcelain suspension insulators required more than a doubling of voltage to decrease time to flashover from 1 microsecond to .1 microsecond. Arresters were found to respond rapidly to steep-front current pulses, but the arrester material itself was found to result in a higher discharge voltage for SFSD pulses. Arresters also showed a delay in turn-on of current following the arrival of a steep-front voltage surge.