Abstract

An experimental study was conducted in a closed loop spray cooling system working with deionized water as a cooling medium, to investigate the effects of surface modification on the spray cooling heat transfer enhancement in the single-phase region. Plain copper surface with diameter 1.5 cm and an enhanced surface with circular grooves were tested under different operating conditions. The volumetric flow rate of the coolant ranged from 115 mL/min to 177 mL/min., and the water inlet temperature was kept between 21–23 °C. Also, the distances between the nozzle and the target surface were varied at 8, 10, and 12 mm respectively. The results show that the distance between the nozzle and the target surface did not have a significant effect on the heat transfer performance for the low flow rates, while it has a slight effect on high flow rates for both surfaces. Also, increasing the liquid volumetric flow rate increases the amount of heat removed, and the heat transfer coefficient for both surfaces. Moreover, the maximum enhancement ratios achieved were 23.4% and 31% with volumetric flow rates of 153 mL/min, and 177 mL/min respectively.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.