Abstract

The high-frequency performance of vertical earth rods is important for designing earthing systems and lightning protection systems. In this work, experimental investigations on the high-frequency and impulse response of vertical earth rods with horizontal electrode enhancements are described. The rod electrode systems are installed at the Cardiff University outdoor earthing test facility and variable frequency tests were carried over the range 50Hz–10MHz. In addition, a low voltage impulse generator was used to inject impulse current of variable magnitude and shape into the electrode under test. The application of ‘4-point cross’ and ‘8-point star’ enhancements to single-rod electrodes have not only demonstrated the expected reduction of low frequency earth resistance but have also helped with a reduction in impedance at higher frequencies. Such enhancements may produce a greater overall benefit compared with extending the length of the rod only. Numerical simulations of the experimental setups agree quite well with test results over a low frequency range but more significant differences are seen at higher frequencies.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.