Abstract

In this paper, an experimental study of the absorption process of water vapor into lithium bromide solution is reported. For the purpose of developing high performance absorption chiller/heater utilizing lithium bromide solutions as working fluid, it brings the largest contribution to improve the performance of the absorber which normally requires the largest surface area among the four heat exchangers of the system. The performance of four types of absorber tubes; bare tube, bumping bare tube, floral tube and twisted floral tube, have been experimentally evaluated. The results show that the floral tube and the twisted floral tube show about 40% higher heat and mass transfer performance than the bare tube which is conventionally used in absorbers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.