Abstract
Spray cooling technology as a high heat flux cooling method is widely used to meet the increasingly cooling requirements, and the enhancement of spray cooling has gradually become a hot spot. In this study, three surfactants of AOS, CTAB and Tween20 with different concentrations were added into pure water to investigate their effects on spray cooling at low temperature range (≤100 °C) in a closed system. The three kinds of surfactants obviously improved the heat transfer performance, which had different optimum concentrations. The lowest mean surface temperature was obtained by CTAB with concentration of 200 ppm. The surface temperature non-uniformity of different surfactants spray was not improved, while the heat transfer deteriorated at high concentrations. In further study, the inclined mode method was used to alleviate the influence of bubble accumulation at high concentrations. The results showed that the inclined spray could significantly enhance the heat transfer capacity of the spray with surfactants and produce the optimum concentration point backward shift phenomenon. Moreover, the inclined spray mode showed a better promotion effect on spray cooling of surfactants with large surface tension.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.