Abstract
The flow behavior of isothermal and non-isothermal wall confluent jets (WCJ) ventilation system was investigated experimentally in a mock-up office environment. Two flow regions were identified: first, a primary region is developed below the supply device, with axis along the inlet wall, and a secondary wall-jet forms along the floor. The velocity and temperature fields were recorded by traversing a hot wire and thermistor anemometers for both primary and secondary regions. The results show self-similarity characteristic of the velocity and temperature profiles for both isothermal and non-isothermal WCJ. Maximum velocity decay and its spreading rate are linear and independent of the inlet airflow rate. Minimum temperature difference and its spread also show linear decay. The spreading rates for maximum velocity are similar in both the primary and secondary regions normal to the inlet wall and floor, respectively, which is consistent with previous studies on wall jets. The variation of draught rating is evaluated via mean velocity, turbulence intensity and temperature. Although the WCJ has slow velocity decay, which enables it to cover almost the entire floor of the test room, the draught is acceptable in the occupied zone according to ISO 7730. PMV (predicted mean vote) and PPD (predicted percentage dissatisfied) are presented for the occupied zone of the room.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.