Abstract

This paper presents results and analysis of an experimental investigation into determining the thermal performance of a flat plate heat pipe using infra red (IR) thermal imaging camera. Steady state and transient temperature distribution of the evaporator surface of the flat plate heat pipe were measured using a single heat source with varied heat flux inputs. For performance comparison, the experimental measurements were also carried out on an identical flat plate heat pipe with a defect and on a solid copper block of similar dimensions. It was shown that temperature excursion on the surface of the fully functioning flat plate heat pipe is less than 3 °C for operating temperatures up to 90 °C and heat flux inputs ranging from 4 to 40 W/cm 2. Furthermore, the thermal spreading resistance of the flat plate heat pipe was found to be about 40 times smaller than that of the solid copper block and flat plate heat pipe with a defect.