Abstract

In hot and humid regions, removal of moisture from the air represents a considerable portion of the air conditioning load. Conventionally, air conditioning systems have to lower the air temperature below its dew point to accomplish dehumidification. Desiccant air conditioners offer a solution to meet the humidity and temperature requirements of buildings via decoupling latent and sensible loads. In this work, the performance of a new desiccant material is investigated experimentally. This desiccant material can be regenerated using a low temperature heat source, as low as 45°C. It also has a unique S-shape isotherm. The effects of the process air stream’s temperature and humidity, the regeneration temperature, the ventilation mass flow rate, and the desiccant wheel’s rotational speed on the cycle performance are investigated. ARI-humid conditions are used as a baseline and the moisture mass balance is maintained within 5%. The results are presented in terms of the moisture removal rate and latent coefficient of performance (COPlat). The results show a desiccant wheel’s COPlat higher than unity when it is coupled with an enthalpy wheel.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.