An experimental investigation was performed on a UHV tower model for the EMTP multiconductor calculation of lightning overvoltage at substations associated with back-flashover at an adjacent transmission tower. The various lightning surge response characteristics were measured on an actual UHV tower, and parameters of a multistory transmission tower model that can reproduce voltages across the insulator strings, voltages of the crossarms, and voltages of the power lines were determined. A value of 120 /spl Omega/ was determined as the surge impedance at each section of the multistory tower model, which closely agreed with the tower surge impedance measured for the UHV tower alone.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.