Abstract

In this work the analysis of the thermodynamic behavior of heat pumps (HP) which supply the energy needed in the public pool at the Aquatic Center of Azcapotzalco was performed. There are 18 installed HP’s but only those needed to provide the energy required are alternately activated. The evaluation was conducted during May and June of 2015. We selected one of the HP to implement temperature and pressure gauges at the inlet and outlet of the compressor. The measurements were made every day at three times, 6:30, 13:00 and 18:00 hours. In a period of 24 hours, 1 000 L evaporated, there was no variation registered overnight, since the pool was covered with plastic to avoid loss of the fluid. The heat pump provided 150 kW to maintain the water temperature at the right level of operation, namely 28 °C. The coefficients of performance (COP) of the HP were 6.39 at 6:30, 7.42 at 13:00 and 7:32 at 18:00 hrs., values which are very close to the one provided by the manufacturer.