Abstract

In this paper, a 1.x-effect (hybrid ejector-absorption refrigeration working between single-effect and double-effect) cycle is evaluated experimentally. Through the use of the ejector, the external heat sources’ grade is reduced. Part of the refrigerant vapor at the outlet of the low-pressure generator is directly entrained by the refrigerant vapor from the outlet of the high-pressure generator to the condenser. The system with 10 kW cooling load is experimentally studied. The COP of the system is 30.0% higher than a single-effect absorption refrigeration system, and generation temperature is at least 20 °C lower than a double-effect absorption refrigeration system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.