Abstract

In this paper a hybrid solar desiccant cooling system which has been designed and installed at the Rockhampton campus of Central Queensland University, Queensland, Australia is experimentally investigated. The cooling system consists of four main components: a solar system, a desiccant dehumidifier, an evaporative cooler and a vapour compression cooling system. In addition, experimental results are presented alongside analytical results of the installed solar desiccant cooling system to evaluate the system performance parameters. The system parameters have been simulated using TRNSYS 16 in two previous studies. The experimental and simulated results are analysed on the basis of energy savings, solar fraction (SF), primary energy used, coefficient of performance (COP) and desiccant system efficiency. Results showed that the installed cooling system at Central Queensland University achieved 18% energy savings with maximum coefficient of performance of 0.83 and 48% desiccant efficiency.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.