Abstract

ABSTRACT In this paper, an experimental device for falling film dehumidification of circular tube is established. The effects of desiccant inlet concentration(30%-40%), velocity(0.01–0.06 m/s), temperature(26–36°C) and air inlet velocity(0.7–1.2 m/s), temperature(26–36°C) and moisture content (15–25 g/kg) on heat and mass transfer dynamic process and the internal detailed temperature, velocity were investigated by experiments and CFD model. The results show that the CFD simulation is in good agreement with the experimental results, with an average error of 4%. Then, the heat and mass transfer and desiccant flow process inside the dehumidifier are analyzed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.