Abstract
The performance of a thermosyphon solar water heater was studied analytically and experimentally. A finite-difference model was used to predict year-round performance. Tests were conducted on an experimental heater subjected to acutal weather conditions in Benghazi, Libya. Satisfactory qualitative and quantitative agreement was found between experimental and predicted results. A storage volume of 60 liters per unit collector area was found to be optimum for Benghazi conditions. The day-end temperature was found to vary between 23° and 51°C for the test period, which occurred in winter, with an average of 41°C.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.