Abstract

This paper investigates the use of a vertical coaxial borehole heat exchanger (BHE), focusing on those consisting of standard geothermal piping material, as a component in a ground-source heat pump system. The results of a lab-scale experiment are used to verify the trends exhibited by a recent semi-analytical model, referred to as the composite coaxial (CCx) model, considering short-term behavior when laminar flow is experienced in the annular space of a coaxial heat exchanger. The discussion on pipe sizes is then expanded upon using the suggested model along with a modified design procedure to compare the performances realized by an example heat pump. A comparison is made here between configurations having various nominal inner pipe diameters while maintaining the same outer pipe. The results of the analysis show that increasing the inner pipe diameter, within the verified limit of the composite coaxial model, will reduce the required length of heat exchanger and increase the overall coefficient of performance realized by the heat pump.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.