Abstract

The thermal performances of an evacuated tube collector (ETC) and flat-plate solar air collector (FPC) are experimentally investigated at different air flow rates. To investigate the performance of the ETC and FPC, experimental set-ups were fabricated. Air was used as a working fluid and tested at the same climatic conditions. The ETC had 15 evacuated tubes with a surface area of 1.66 m2. The experimental set-up consisted of a header with a hollow pipe (square pipe) in the centre through which the air flowed. The flat-plate collector had a surface area of 1.35 m2. The FPC had a black painted absorber sheet which divides the collector into two sections. The air flowed through the upper and the lower sections parallel to the collector to minimize the overall heat loss. The temperature of the outlet air depends on several factors along with the airflow rate and the intensity of the solar radiation. It was found that during the day at high flow rates, the efficiency of the ETC varies from 0.12 to 0.5, and for the flat plate it was from 0.29 to 0.68. The maximum temperature of the air was 56.7°C for the ETC and 25.7°C for the FPC.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.