Abstract

ABSTRACT This paper presents the results of the monitoring and analysis of the dynamic behaviour of the Gorino Ferrarese (Ferrara, Italy) water distribution system. The network is subjected to ordinary operational conditions, (i.e. no manoeuvres on pumps or valves are considered), the aim being to show that user demand may generate frequent and not negligible pressure variations. Pressure and discharge were monitored for two days in different sections of the network. The dynamic behaviour of the system is then characterized by analysing the pressure changes at the measurement sections in the time and frequency domains. Such analyses highlight that pressure signals are characterized by long-term changes (low-frequency) on which shorter period (high-frequency) ones overlap. Long-term oscillations show a similar trend at all measurement sections and are characterized by certain dominant frequencies, linked to the topological and mechanical characteristics of the network. Instead, high-frequency pressure fluctuations related to user activity vary in amplitude both spatially and temporally.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.