Abstract

A test facility for the experimental investigation of the R744 vapour compression rack equipped with a multi-ejector expansion work recovery module was designed and manufactured. A comparison of the R744 multi-ejector refrigeration system with the R744 parallel compression system at the same test facility was carried out based on the energy performance characteristics of refrigeration capacity, power consumption, COP, and exergy efficiency. Apart from the system performance comparison, the influence of the pressure level in the flash tank on the system performance for the two alternatives was analysed. The experimental results indicate COP and exergy efficiency improvements of the multi-ejector refrigeration system up to 7% and 13.7%, respectively. The highest values of COP and exergy efficiency were obtained by a multi-ejector refrigeration system with the tank pressure lift close to the maximum value possible to operate the multi-ejector expansion module. The values of the effective compressor efficiencies were significantly different, depending on the operation module (cooling load and heat rejection conditions).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.