Abstract

This study investigated the performance of a typical mobile air conditioning system using R134a and R1234yf as the working fluids under different working conditions. The system is composed of a microchannel parallel flow condenser, a laminated plate evaporator, a variable displacement compressor, and a thermal expansion valve. The different working cycles of each refrigerant were comprehensively compared. The optimum refrigerant charge amount of the R1234yf system was approximately 95% of the R134a system during drop-in tests. The performance of the R134a system was a little higher than that of the R1234yf system. The cooling capacity and system coefficient of performance of the R134a system were 12.4% and 9% larger, respectively. This result is mainly because of the thermophysical property differences between the two refrigerants and the improper expansion valve opening of R1234yf. Analysis on the whole cycle revealed that the R1234yf system could obtain a higher evaporating pressure and a larger superheat and subcooling. Redesigning the expansion valve for R1234yf could improve performance of the system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.