Abstract
This paper presents the results of a series of laboratory tests of CLT end-grain moisture uptake and dry-out. We put CLT test details (TDs) in direct water contact from the end-grain edge and then left the TDs to dry for two weeks in the laboratory and in an outside shelter. Half of the TDs had their wet sides attached to another CLT detail. Fibre saturation point was quickly reached in the bottom part of the TDs during the seven-day water contact. A tendency of increasing moisture content (MC) was up to 90 mm from the wet edges, but we did not record MC levels above the critical level at that height. However, MC exceeded critical levels at 60 mm from the water level. The measured water absorption coefficient Aw was 3.51×10−3 kg/m2-s0’5. Drying was negligible for the TDs which were in contact with another CLT detail. Thus, moisture dry-out is very complicated in joints where the CLT end-grain is covered, such as the exterior wall to foundation or intermediate ceiling connection. The dry-out of CLT is not expected in a cold and humid outdoor environment once the CLT end-grain has absorbed moisture even with wet edges exposed to air.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.