Abstract

Mainly HFCs are nowadays used as refrigerants in commercial household heat pump tumble dryers; it is however crucial to look for long-term alternatives with low environmental impact. Hydrocarbons are considered a suitable alternative for this application. According to their characteristics and based on theoretical analysis, R290 and R441A were selected as substitutes of R407C in a commercial unit. While maintaining exactly the same components, the compressor was changed to comply with the required heating capacity and the expansion device was modulated to meet proper working conditions. Experimental results confirmed that R290 meets the reference energy performances; at the specific conditions, R441A underperforms R407C, due to increased compressor consumption. Technological focus on components is therefore important when refrigerant replacement takes place.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.