Abstract
This paper provides an experimental analysis of flow boiling heat transfer in four finned evaporators with different aspect ratio and heated length have been tested. R245fa was the refrigerant chosen as working fluid for its good thermal characteristics. The imposed heat flux at the footprint covered a range from 30 to 330 kW/m2, while the fluid mass fluxes within the channel varied in a range between 17 and 225 kg/m2 s. The hydraulic diameters of the investigated evaporators were 1.15 mm and 2.09 mm, with aspect ratio (channel width/channel height) respectively of 0.3 and 0.72. Thanks to the measuring apparatus, heat transfer data were collected and then processed to calculate the local heat transfer coefficients, using the fin array heat transfer model. These local values of the heat transfer coefficient were then compared with those calculated from existing correlations for mini-micro channels flow boiling and the Mean Absolute Percent Error was finally assessed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.