Abstract

In this paper, one novel heat pipe solar adsorption chiller with mass-heat recovery was designed. 65 kg of micro-porous silica gel was used as adsorbent in each adsorbent bed. The influence of operating conditions on the chiller was investigated. The chiller was applied in Green Building in Dezhou city (north latitude of 36°41′) in China. Under the typical summer weather conditions, the average thermal efficiency of solar collector, the average COP (coefficient of performance) of the adsorption refrigerator and the average solar COP of the system are 0.36, 0.44 and 0.16, respectively. The results show that the adsorption cooling performance rises as the hot water inlet temperature, chilled water outlet temperature rise, and it declines as the cooling water inlet temperature rises. The performance can be improved by mass-heat recovery significantly. When the hot water inlet temperature, cooling water inlet temperature, chilled water outlet temperature are 79.0 °C, 25.4 °C, 13.7 °C, respectively, the cooling capacity and COP are 17.9 kW and 0.63, respectively.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.