Abstract

Indirect evaporative cooling is an effective way to increase energy efficiency of air conditioning systems. This technology is particularly suitable for data centers applications, where the indoor temperature can be higher than the one adopted in residential and commercial buildings. In this work an indirect evaporative cooling system based on a cross flow heat exchanger has been widely tested. The system has been designed in order to minimize water consumption, with water mass flow rate between 0.4% and 4% of the secondary air one. On the whole, 112 experiments have been carried out in different working conditions of data centers. The effects of variation of water flow rate, humidification nozzles setup and secondary air temperature, humidity and flow rate have been widely investigated. Results put in evidence that performance is slightly dependent on nozzles number and size but it is strongly influenced by the water flow rate. In addition, nozzles in counter flow arrangement perform better than in parallel flow configuration. Depending on working conditions and equipment setup, the wet bulb effectiveness varies between 50% and 85%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.