Abstract
The heat transfer and the pressure drop are experimentally studied on the extended heating surfaces with transverse fins for flow direction placed in the air channel of rectangular cross section. From the results of experiment on the effects of fin whose pitch and height are p and l respectively, channel height and Reynolds number, empirical equations for the heat transfer coefficient and the friction factor are presented. It has been shown that the ratio of fin pitch to fin height p/l is a most important factor for the heat transfer and pressure drop performance. In the case of the value of p/l=1.2∼1.6, the finned surface shows the most effective performance. The flow patterns between fins of the surface are observed and the effect of fin materials is also studied experimentally.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.