Abstract
Four failures of large EHV auto-transformers on the AEP system are described. The failures were initiated by flashovers in the no-load tap changer during system faults. Investigations and tests attribute the flashovers to part-winding resonance. Test data is presented for various terminal conditions and wave shapes corresponding to system transient conditions. The relationship of these tests to ANSI standard dielectric tests is discussed. Corrective measures for existing transformers include arresters tied to an internal crossover connection and capacitor banks connected to the delta tertiary windings.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.