Abstract

In this paper, exergy analysis was implemented to improve the inter-city bus air-conditioning (AC) system design. Firstly, an inter-city bus with a passenger capacity of 56 people was selected and then its hourly cooling load capacity was determined with the help of cooling load hourly analysis program (HAP). Analyses were performed for different air mixing ratios (MRs) and seasons. Coefficient of performance (COP), exergy efficiency (ψ) and exergy destructions (Ėxdest) of whole system and its each sub-units were evaluated. Results demonstrated that the atmospheric air temperature and air MR substantially affect the inter-city bus AC systems' performance. According to the results obtained for July, when air MR is 0.5, maximum exergy destruction value was calculated as 6.96 kW at compressor. Exergy destruction values were computed as 2.78, 2.61 and 0.99 kW for evaporator, condenser and expansion valve, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.