Abstract

This paper deals with exergoeconomic analysis of a dormitory heated by a conventional boiler in a central heating system. The energy and exergy flows are examined from the generation stage to the envelope of the building. The energy and exergy flows between the stages are obtained using a predesign tool for an optimized building design. Exergetic and exergoeconomic analyses of some heating equipment are comprehensively evaluated. A conventional boiler and a water heater in the central heating system are considered in the analysis. Based on the analysis results obtained, the total exergy input rate is calculated to be 1455kW while the largest exergy loss rate is found to be 987.6kW. Exergetic efficiencies of the conventional boiler and the water heater are also obtained to be 15.6% and 20.4%, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call