Abstract

This study deals with energy/exergy, exergy cost analyses and sustainability assessment of a low exergy heating system. In this study, an indoor sports hall with a volume of about 28,180m3 and a floor area of 2366m2 is considered as a case study. In this context, three different heating options are investigated, namely, (i) a conventional boiler, (ii) a condensing boiler and (iii) an air heat pump as driven by fuel-oil, natural gas and electricity, respectively. In this regard, an energy and exergy analysis is employed to assess their performances and compare them through energy and exergy efficiencies and sustainability index. Also, total exergy costs based on the considered systems with three different fuels are determined and compared with each other. Overall exergy efficiencies of the heating systems are found to be 2.10%, 2.33% and 2.42% while their corresponding sustainability index values of the analyzed cases are calculated to be 1.021, 1.024 and 1.025 for cases 1 through 3, respectively. Total exergy costs of the considered systems are obtained to be Ccase1>Ccase3>Ccase2. Based on the exergy cost analysis results, the most cost effective system is Case 2.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.