Abstract

An exergetic analysis was made to a GAX refigeration cycle. This GAX refigeration system was designed to produce 10 kW cooling power using two thermal sources, LP gas and solar energy, the system used to be air cooled avoiding the cooling tower. The methodology of exergetic cost was used to identify which part of the system generates the most irrerversibilites. The results indicates the absorber, the generator and the rectifier are the most irreversible components of the system. The sum of these three components irreversibilities represent the 58% of the total irreversibility. The exergetic cost was calculated for all of the flows of the GAX refrigeration cycle, the unit exergetic cost of the heat flow at the evaporator is 6.8. The highest exergetic cost was found in the solution coming out of the rectifier to the generator heat exchanger.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.