Abstract

Performance of two fire zone models CFAST and BRI2 on simulating small compartmental fires were studied experimentally in a fire chamber with a vent of varying size and height above the floor level. The chamber is of length 4.0 m, width 3.0 m and height 2.8 m. Burning tests were carried out with wood cribs and methanol to study the pre-flashover stage of a compartmental fire and the effect of ventilation. The mass loss rate of fuel; temperature distribution of the compartment; air intake rate; and oxygen concentration at the outlet openings were measured. The heat release rates of the fuel were calculated by using the mass loss rate and the oxygen consumption methods. Differences between the two approaches in getting the heat release rate on the predicted results by the zone models were also studied.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.