Abstract

Metal-oxide surge arresters are one of the most important equipments for power system protection against switching and lightning over-voltages. Surge arresters leakage currents increase by the operating time. In this study, the important factors on leakage current variations such as surface contamination, ultraviolet ageing and varistor degradation have been studied. To accomplish this purpose, experimental tests have been performed on various polymer housed surge arresters. Fast Fourier transform analysis has been performed on measured leakage currents. Results show that ultraviolet radiation and varistor degradation affect resistive harmonic components, especially the third and fifth harmonics. Moreover, it is observed that surface contamination has influence on fundamental harmonic variation more than ultraviolet ageing. In addition, combination of ultraviolet radiation and pollution had more effect on leakage currents. The investigation and the discussion of the results can be used to easily analyse arresters condition leading to effective schedule maintenance.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.