Abstract

• Lightning response of grounding electrodes is assessed using FDTD. • The effect of absorbing boundary conditions is shown. • Liao's 3rd order and CPML lead to results better than those of Liao's 2nd order. • Modeling the soil as a Debye medium leads to results closer to those of HEM model. • 6 poles are enough to represent the frequency-dependence of soil parameters. This work evaluates the influence of the absorbing boundary conditions (ABC) and the representation of frequency-dependent soil parameters on the assessment of the lightning performance of grounding electrodes using FDTD-based computational model. The results in terms of grounding potential rise (GPR), grounding impulse impedance (Z P ), and low-frequency grounding resistance (R LF ) showed a better agreement with those calculated by the HEM model when Liao's 3rd order and Convolutional perfect matched layer (CPML) boundary conditions were assumed. The increase of the simulation space contributed to improve the results related to Liao's 2nd order but demanding a longer computation time. Despite the observed improvement, they are still far from those provided by the other ABC. Modeling the soil as a Debye medium to consider frequency-dependent soil parameters leaded to lightning response of grounding electrodes very close to that provided by the HEM model. In terms of Z P , the largest percentage difference was about 6%. Also, the work indicated that the adoption of 6 poles identified by the MATLAB function invfreqs was enough to represent the frequency-dependence of soil parameters, contributing to decrease the computation time.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call