Evaluate the effect of the fresh air purification system on the improvement of indoor PM2.5 levels in a primary school classroom in Jinan City, Shandong Province. Our purpose is to explore the optimal operating time of the fresh air system and the main factors that affect the fresh air purification system to improve indoor air quality. From December 9, 2019 to December 10, 2019, two classrooms of the same area on the third floor of a primary school building in Jinan City, Shandong Province were selected as monitoring points. During the operation of the fresh air purification system, the PM2.5 concentration in the classroom is reduced by an average of 48.1%-61.5% compared to the outdoor PM2.5 concentration. After running for about 2 hours, the indoor PM2.5 concentration decreased to a relatively stable concentration level. The operating time of the fresh air purification system, student activities between classes, indoor temperature, indoor relative humidity, and outdoor PM2.5 concentration are important factors that affect the indoor particulate removal rate. In the case of a certain amount of fresh air and indoor area, closing doors and windows and appropriately extending the operation time of the fresh air purification system can improve the air quality in the classroom to a certain extent and protect the health of students.