Abstract
Islanding is undesirable because it may poses safety hazard to utility service personnel and also it can lead to asynchronous reclosure which will damage the equipments. Grid connected PV inverters are required to have passive islanding detection and protection methods that cause the PV inverter to stop supplying power to the utility grid. The active and reactive power equations and Non-Detection Zone of Over/Under Voltage Protection and Over/Under Frequency Protection methods for grid connected PV system under constant power mode inverter are derived and analyzed in this paper. Analyses indicate that the behavior of the PV system at the time of disconnection are depend on the mismatch power, these results also indicate the Non-Detection Zone of Over/Under Voltage Protection and Over/Under Frequency Protection methods are considerable large and include balanced islands which reduces the dependability of these passive methods.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.