Abstract

The commutation failure is one of the most common faults in high voltage direct current transmission (HVDC) systems. The research on the HVDC commutation failure has made some achievements at home and abroad. However, the influence of harmonic on the commutation failure of HVDC has not been studied thoroughly. Based on the commutation process of HVDC and the commutation voltage-time area analysis, a harmonic influence factor is derived, and the influence of harmonics on the commutation process in HVDC is quantitatively analyzed. The evaluation index of the risk of commutation failure due to harmonics, which is defined as the harmonic influence superposition E sup , is proposed, and a method using E sup to evaluate the risk of commutation failure caused by harmonic voltage is given consequently. Finally, based on the PSCAD/EMTDC electromagnetic transient simulation platform, the proposed evaluation indicators are simulated and verified.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.