Abstract

Variable-frequency drives (VFDs) with diode front-end rectifiers are typically equipped with a resistor-contactor arrangement to limit the inrush current into the dc-bus capacitors, thereby providing a means for soft charging the dc-bus capacitors. Because of the mechanical nature of the magnetic contactor typically used in VFDs, there exists a concern for fatigue. In addition, during a brownout condition, typically, the contactor remains closed, and when the voltage recovers, the ensuing transient is often large enough to possibly cause unfavorable influence to surrounding components in the VFD. Many researchers and application engineers have thought about this issue, and many are actively seeking nonmechanical solutions in a cost-effective manner. In this paper, a new topology to soft charge the dc-bus capacitor is proposed. Other techniques that have been evaluated are also introduced. The relative advantages and disadvantages are discussed. Experimental tests to show the feasibility of the proposed idea are also provided.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.