Abstract

It is essential to have an effective treatment program and control methodology for a nuclear power plant cooling water system. As the accumulationand growth of cooling water deposits reduce the overall heat transfer coefficient and have an adverse effect on the operation of equipments,plant availability, production, and maintenance cost. The study aims at evaluationof using a primary treatment unit debris filter as a controllingof fouling formation, in a nuclear power plant located in coastal area. Selecting Sedi kerir, and Sidi Abdelrahman cooling water channel for the proposed nuclear power plant. Samples of the two selected sites had been taken and some physicochemical and biological parameters were analyzed such as (pH, total alkalinity, total dissolved solids, suspended solids, temperature and total count of microalgae). A mathematical model has been used also in order to help in evaluation of the suggested pretreatmentunit. The results has showed that sea water temperature used at the two selected sites (Sidi kerir, and Sidi Abdelrahman below 1250F that mean low fouling factor, also the measured physicochemical and biologicalparameter concentrations at the proposed two selected sites increase the probability of fouling formation at these sites. As a using of suggested debris filter pretreatment unit for cooling water at the two selected sites, will help in decreasing the probability of fouling formation at these site.