Abstract

Most of the grid codes generally require the Distributed Energy Resources (DERs) in order to remain connected throughout short-circuit grid faults and to provide the grid voltage support through reactive power-based regulation via additional Reactive Current Injection (aRCI) during the Low Voltage Ride Through (LVRT). It has been found out that the X/R ratio of the DER connection affects the effectiveness of the voltage support in improving the voltage sags. In this paper, the theoretical analysis of the system's X/R ratio impact on the effectiveness of the investigated voltage support is given. Furthermore, with the help of a MATLAB Simulink-based simulation study, the theoretical analysis is verified. The research is meant to substantiate a clear understanding of the effect of low X/R ratio to the voltage support in improving voltage sag. Finally, the rising number of the DERs on the distribution grid has been linked to the weakening of the grid strength, which often causes the system instability following the post-LVRT state. From the simulation, it has been found out that on a weak grid, the instability during the post-LVRT period could be prevented through correctly adjusted reactive power-based voltage regulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.