Abstract
The authors carried out an outdoor exposure test and the 5000h multiple stress test to ethylene vinyl acetate (EVA) polymer composite insulator used for 22kV distribution line and an attempt was made to estimate the acceleration factor of the 5000h multiple stress test corresponding to the climate condition of the Kyushu area. By comparing dryband arc cumulative charge of leakage current at 5000h multiple stress test with that in the outdoor exposure test, the authors estimated the acceleration factor of the 5000h multiple stress test to be about 20 times. The acceleration factor was found to almost agree with the evaluation result of the absorption of hydroxyl group by FT-IR analysis and the surface roughness of the insulator, respectively. Finally, for the electrical property, the expected life of EVA insulator that the authors developed was confirmed to be more than 40 years.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.