Extremely low-frequency magnetic fields (ELF-MFs) have raised some concerns due to their possible effects on workers' health. In this study ELF-MFs were measured in different units of the thermal power plant based on gridding the indoor space. The exposure level was measured by spot measurement based on the IEEE Std C95.3.1 and then simulated in units with the highest magnetic field intensity by using ArcGIS software. The operators and balance of plant (BOP) technicians (12.64±9.74μT) and office workers (2.41±1.22μT) had the highest and lowest levels of both measured and estimated ELF-MFs exposure. The highest measured ELF-MFs were in the vicinity of the power transmission lines in the transformers' building (48.2 μT). Our simulation showed the high and low exposure areas and ranked exposure well; but, the actual measurements of ELF-MFs exposure were in all cases higher than the estimated values, which means we still need to improve our estimations.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.