Abstract

This article covers the analysis of voltages induced on the conductors of a de-energized circuit of a multi-circuit, multi-voltage HVAC transmission line. As a result of the multiplied interactions between the circuits in such lines, the expected electrical shock currents (touch currents) to which a lineman performing live work on such a line may be exposed are determined. A number of supporting structures of three- and four-circuit lines with various degrees of geometric asymmetry are analyzed. Analyses have shown that in multi-circuit lines in which circuits of different voltages are carried on a common structure, despite the outage of one of the circuits, touch voltages and electrical shock currents (touch currents) exceeding the permissible values can be expected on its conductors, endangering the safety of the lineman. The arrangements of s in such lines that provide the smallest values of touch currents are indicated.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.