Enclosure burn-through in SF6 insulated substations is a rarely occurring event; however, in view of the possibly damaging effects to equipment and personnel, its probability of occurrence warrants a closer examination. This paper presents a model for estimating the likelihood of enclosure burn-through or pressure relief disc bursting during an in-service fault in SF6 substations. Results of a simulation show a 25% burn-through probability per fault in substations with the most probable fault currents in the 50 kA range. The probability of personnel being exposed to the hazardous arcing by-products is discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.