Abstract

Algorithms are well presented for estimation of harmonics and their elimination in a three phase system for power quality improvement. This paper presents the application of KF-Adaline Algorithm for estimation of power system harmonics and shunt active power filter with hysteresis current controller based on space vector modulation for perfect elimination of harmonics. The space vector modulation (SVM) based hysteresis current controller (HCC) combines both the advantages of SVM and HCC. This controller determines a set of space vector from a region detector and then applies a space vector according to the Hysteresis current controller. Reference current extraction is done by the synchronous detection technique which is compared to the actual current and the error current is fed to the Shunt Active Power Filter (SAPF). Shunt Active Power Filter manages to provide better compensation signals to eliminate the harmonics for power quality improvement which is fed to the distribution system. Simulation results are provided to verify the better performance of SAPF due to the proposed controller.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.