Abstract

Synchronous generators were manufactured with asphalt bonded, mica flake insulation from 1917 to the 1950s. There is a large fleet, perhaps two thousand, of these machines still in service today. This paper presents the results of a well documented series of field tests, many to failure, on 20 asphalt-mica insulated fossil fuel and hydroelectric synchronous generators on the American Electric Power system and laboratory tests on over 30 spare asphalt-mica stator bars and coils at AEP's Dolan Laboratory. The paper clearly shows that a straightforward AC overpotential test and a simple graphical evaluation and analysis can be used to confidently determine the remaining service life of asphalt bonded, mica flake insulated synchronous generators that have been well maintained and operated within design limits.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.