Abstract

According to the water coolant quality standards, the makeup water supplied to a thermal power plant’s (TPP) steam-generating systems must not have any content of free carbonic acid. As a rule, free and partially bound carbonic acid is removed from makeup water supplied to the power-generating boilers at TPPs in atmospheric deaerators. Their performance as decarbonizers can be evaluated by measuring the pH values of water supplied to the deaerator and of the deaerated water. A procedure for calculating the residual concentration of carbonic acid in deaerated water and the decarbonization effect from the change in the pH value (ΔpH) is presented together with an example of calculation carried out by specialists of the Ivanovo State Power Engineering University based on a long-term industrial experiment performed on DSA-300 atmospheric deaerators.