Abstract

When an electric arc is generated in transformer oil, a strong overpressure may rapidly develop in the tank, especially for low-impedance faults. This paper presents the test method and results obtained in a project aimed at assessing the human and environmental risks associated with this type of fault. Limit energy and pressure values were defined in terms of different safety levels. The best method of limiting the energy and pressure at a safety level in the transformer tank during internal faults of greater than 1.7 kA is to protect the transformer with a current limiting fuse. Other ways to increase the mechanical withstand of transformer tanks under such faults are also discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.