Abstract

The article is concerned with the operation of electric power quality meters and analyzers when incorrectly installed on a three-phase electrical network. An analytical study of the meter’s errors under the conditions of faulty installation was carried out. All possible types of installation errors are considered according to the proposed classification, as well as possible combinations of a pair of installation faults simultaneously. Classification of installation faults is also proposed. Matrix expressions are derived that allow modeling of any type of installation faults to quantify power and symmetry measurement errors. The proposed method allows to obtain quantitative signs that can identify a specific installation fault. The results of this study can help the development of an algorithm for the automatic detection of installation faults and their correction. The analytical results were confirmed by simulation studies on a three-phase network model in the MATLAB/SIMULINK environment. Experimental results, obtained from a commercial power quality analyzer operated under controlled laboratory conditions, are also reported.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call