Abstract
DC bias widely exists in power system. In order to analyze its influence on metering current transformer (MCT), a new digital simulation model based on Preisach theory is constructed firstly. Using this digital model, the ratio error and angle error of a running MCT are calculated under different levels of DC bias. Simulation results show that the current DC bias in power system has only little influence on the error of MCT.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.