Abstract

In this paper, the performance of silicone rubber composites containing 0, 10 and 30 wt % loading of silica filler is investigated in the initial-tracking voltage test method of the inclined plane test under AC and DC showing the most inferior erosion class under +DC followed by -DC and then AC. DC as compared to AC dry-band arcing characteristics are analyzed by conducting leakage current measurements prior to and after the inception of dry-band arcing. At high test voltages, instability of the contaminant rivulet is found to be an important factor in the development of dry band arcing and, consequently, biasing the test outcomes when equal voltages of rms AC and DC are selected. The initial tracking voltage in ASTM D2303 is, therefore, proposed as a reliable approach by which +DC and -DC test voltages can be reliably selected. A coefficient of variation parameter is also proposed as a useful mean of selecting the equivalent DC voltages, and the validity of the parameter is verified experimentally using the initialtracking voltage test method. Erosion in the constant voltage method is investigated under DC by applying the equivalent voltages and compared to AC. Based on this methodology, it is suggested that an improvement in silicone rubber compositions is needed for DC. Moreover, the need to select the creepage distance of polymer insulators designed for AC, yet to be used under DC, with reference to tracking/erosion performance is highlighted.